ZipTap Report homeCheck my ZIP

What’s in Dallas tap water

Dallas Water Utilities (DWU), from its 2025 Water Quality Report and EPA’s federal record.

PWSID TX0570004 1,356,479 people served (SDWIS) Surface water Checked Nov 20, 2026
1,356,479people served, per EPA SDWIS
1.09 ppblead, 90th percentile in EPA SDWIS (period ending Dec 31, 2024)
0health-based violation records in SDWIS (all years)
0SDWIS violation records of any type since 2021

Dallas’s report says the city uses surface water from seven sources: the Elm Fork of the Trinity River and lakes Ray Roberts, Lewisville, Grapevine, Ray Hubbard, Tawakoni and Fork, treated at three plants. DWU says its water “meets or exceeds all state and federal requirements for water quality.” The report also says DWU’s service line inventory “contains no known lead service lines,” and that property owners are responsible for the private portion of the line. Source: 2025 Water Quality Report, checked Nov 20, 2026.

Dallas Water Utilities (DWU): highlights from the 2025 Water Quality Report. Values as printed by the utility.
SubstanceReported valueRange / detailLimit or goal shown in the reportFilter certification that covers it
Lead (home taps, 90th percentile, 2024)1.1 ppb0 sites exceeding the action levelAction level 15 ppb; goal 0NSF/ANSI 53NSF/ANSI 58
Claim: “Lead Reduction”
Copper (home taps, 90th percentile, 2024)0.39 ppm0 sites exceeding the action levelAction level 1.3 ppmNSF/ANSI 53NSF/ANSI 58
Claim: “Copper Reduction”
Total trihalomethanes (TTHM)19.7 ppb (highest LRAA)6.5 – 21.0 ppbMCL 80 ppbNSF/ANSI 53NSF/ANSI 58
Claim: “Trihalomethanes (TTHM) Reduction”
Total haloacetic acids (HAA5)15.1 ppb (highest LRAA)1.4 – 16.4 ppbMCL 60 ppbNo HAA5 claim category in NSF’s listing search
Nitrate (as N)0.671 ppm (average)0.587 – 0.802 ppmMCL 10 ppmNSF/ANSI 58
Claim: “Nitrate/Nitrite Reduction”
Fluoride0.627 ppm (average)0.553 – 0.686 ppmMCL 4 ppmNSF/ANSI 58
Claim: “Fluoride Reduction”
Total chlorine residual (disinfectant)2.97 ppm (annual average)2.75 – 3.18 ppmMRDL 4 ppmNSF/ANSI 42
Claim: “Chlorine Reduction / Chloramine Reduction”
Bromate0.00 ppb (highest LRAA)0 – 0 ppbMCL 10 ppb (running annual average)No bromate claim category in the NSF listing data we checked
PFASNot stated in this reportThe 2025 report’s tables list no PFAS resultsNot statedNSF/ANSI 53
Claim: “PFOA Reduction / PFOS Reduction / Total PFAS Reduction”

The disinfection byproduct rows sit under the report’s “Highest LRAA” heading; the fluoride, nitrate and chlorine figures are in its average column (chlorine is marked “as annual average”). Lead and copper are from 2024 sampling, the latest year the table shows, and are the “90 percentile value in the distribution system.” The report does not say whether its total chlorine residual is free chlorine or chloramine, so the filter column shows both NSF claim names. Total coliform: highest monthly positive 1.8%; turbidity: highest single measurement 0.16 NTU, 100% of monthly readings meeting the limit. Its unregulated-contaminant table lists four trihalomethane compounds (for example chloroform, average 4.57 ppb) and no PFAS. Filter column: claim names and standards from NSF’s certified-product listing search, checked Nov 20, 2026. A standard number alone is not enough: the specific model must be listed for that claim.

What these numbers can and cannot tell you

These are the utility’s system-wide figures. Lead usually comes from a building’s own pipes and fixtures, so your tap can differ from the 90th percentile. EPA’s lead page explains this: EPA, Basic Information about Lead in Drinking Water, checked Nov 20, 2026. For health questions, talk to your doctor.

Lead at home taps: EPA’s federal record

90th-percentile lead (ppb) in EPA SDWIS for TX0570004, last 3 sampling periods, against the 15 ppb action level. Source: EPA Envirofacts LCR_SAMPLE_RESULT and LCR_SAMPLE, checked Nov 20, 2026.Action level 15 ppb02018020211.092024
90th-percentile lead (ppb) in EPA SDWIS for TX0570004, last 3 sampling periods, against the 15 ppb action level. Source: EPA Envirofacts LCR_SAMPLE_RESULT and LCR_SAMPLE, checked Nov 20, 2026.
Lead 90th percentile by sampling period, EPA SDWIS (TX0570004)
Sampling period90th-percentile lead
Jan 1, 2016 – Dec 31, 20180 ppb
Jan 1, 2019 – Dec 31, 20210 ppb
Jan 1, 2022 – Dec 31, 20241.09 ppb

Violations in EPA’s record

SDWIS lists 1 violation records for this system in total. Most are monitoring or reporting records. The health-based ones are below, with EPA’s own labels and status.

No health-based violation records appear in SDWIS for this system.

Sources: EPA Envirofacts VIOLATION table, checked Nov 20, 2026; code labels from EPA’s SDWA reference code file (ECHO SDWA data download, checked Nov 20, 2026). The full federal report: EPA ECHO detailed facility report.

Which filter to look for, based on this report

Match the items you care about to a model that is listed for that claim. Our filter guide explains each type. Two items here are worth knowing:

ZIP codes we match to Dallas

44 ZIP codes lie at least 90% inside Dallas by land area (Census 2020): 75201, 75202, 75203, 75204, 75206, 75207, 75208, 75209, 75210, 75211, 75212, 75214, 75215, 75216, 75217, 75218, 75219, 75220, 75223, 75224, 75226, 75227, 75228, 75229, 75230, 75231, 75232, 75233, 75235, 75236, 75237, 75238, 75240, 75241, 75243, 75246, 75247, 75248, 75249, 75251, 75252, 75270, 75287, 75390.

Reserved

Space reserved for a future, clearly labeled filter retailer link. No affiliate links are live on this site.

Questions

Is Dallas tap water safe to drink?

We do not grade or certify any water system, and a system-wide report is not a test of your own tap. What the records show: the 2025 Water Quality Report lists lead at home taps at 1.1 ppb (90th percentile) against the 15 ppb action level, and EPA’s SDWIS database lists 0 health-based violation records for TX0570004 across all years. Lead usually comes from a building’s own pipes, so the only way to know your tap is to test it. For health questions, talk to your doctor.

How much lead is in Dallas tap water?

The utility’s report lists 1.1 ppb at the 90th percentile of home-tap samples (0 sites exceeding the action level). EPA SDWIS shows 1.09 ppb for the sampling period ending Dec 31, 2024. The federal action level is 15 ppb and the health goal is zero.

Does Dallas tap water have PFAS?

The 2025 Water Quality Report does not list PFAS results in its tables, so we cannot say. Ask the utility, and see our PFAS page for where the federal rule stands and which NSF claims cover PFOA, PFOS and total PFAS.

What water filter reduces lead in Dallas?

Look for a model listed by NSF for “Lead Reduction”. In NSF’s listing search that claim appears under NSF/ANSI 53 and NSF/ANSI 58 (reverse osmosis). The standard number alone is not enough: the exact model must be listed for the claim.

Which ZIP codes does this Dallas page cover?

44 ZIP codes lie at least 90% inside Dallas by land area in the Census 2020 relationship file: 75201, 75202, 75203, 75204, 75206, 75207, 75208, 75209, 75210, 75211, 75212, 75214 and more (full list above). Check the utility name on your water bill to confirm your system.

Sources

  1. 2025 Water Quality Report (Dallas Water Utilities (DWU)) (dallascityhall.com, checked Nov 20, 2026)
  2. Report page (dallascityhall.com, checked Nov 20, 2026)
  3. EPA Envirofacts WATER_SYSTEM TX0570004 (data.epa.gov, checked Nov 20, 2026)
  4. EPA Envirofacts VIOLATION TX0570004 (data.epa.gov, checked Nov 20, 2026)
  5. EPA Envirofacts LCR_SAMPLE_RESULT TX0570004 (data.epa.gov, checked Nov 20, 2026)
  6. NSF certified drinking water treatment units listing search (info.nsf.org, checked Nov 20, 2026)
  7. U.S. Census 2020 ZCTA to place relationship file (www2.census.gov, checked Nov 20, 2026)